Contact: Mr Feng
Tel:8613519187272
Web:http://www.xaapt.com
You can visit our website to get more information about us.
12KV, Fully automatic
All-in-One, free software
High noise suppression
High Accuracy
Designed for various work environments
Ultra long life cycle
36-month product warranty
Description:
Model DF902A Automatic 12kV Capacitance & Dissipation Factor Test Set is designed to measure dissipation( Dielectric Loss factor/DF/tgδ) or power factor(PF/cosφ ) in heavy electromagnetic interference environment such as in power plants or substations.
Its main specimens: Power transformer, Distribution transformer, Instrument transformer, Bushings, circuit breakers, Surge arrestors, capacitors, Motors and Generators.
Its test capabilities: Power factor(PF/cosφ), Dielectric Loss factor/DF/tgδ, Capacitance.
Product Features:
Fully automatic, easy to use;
All-in-one Structure, Lightweight, rugged & compact, true portability
High noise suppression based on the frequency conversion and digital filter technique, its test accuracy can be ensured even the ratio of interference current to specimen current is 2:1(200%).
High speed A/D converters, processed by a DSP. self-calibrating, accuracy standard capacitor, ensure Model DF902A high accuracy
l All the input resistance is less than 2 Ohm, the attached capacitance of connection cable is negligible
Designed for various work environments, in the field, in the laboratory, in a test van;
Protections: output protection, input protection, grounded protection, fault protection
Model DF902A has multiple functions:UST / GST /GSTg, all these functions with its main unit
Using an external high voltage power supplies over 12kV or 5A
100 groups of data storage. RS232 is available; Micro-Printer inside
Ultra long life cycle, average 10 years
Multi Language Version available, English, French and Russian
Specifications
Accuracy:
Cx ±(reading×1%+1pF)
DF tgδ ±(reading×1%+0.00040)
PF cosφ ±(reading×1%+0.00040)
Interference: Ratio of interference current to specimen current is 2:1 ( 200% )
Capacitance Range:
Internal HV 3pF~60000pF / 10kV,60pF~1uF/0.5kV
External HV 3pF~1.5uF/10kV
Resolution 0.001pF, 4 digitals
tgδ Range: No limit, Resolution 0.001% (C/L/R specimen is automatic recognized)
Input current range: 10μA~5A
Internal HV: 0.5~12kV / 200mA (max)
Accuracy: ±(reading×1%+10V)
Control mode: Rise or fall smoothly
Frequency: 45Hz, 50Hz, 55Hz, 60Hz, 65Hz single frequency
45Hz/55Hz, 55Hz/65Hz, 47.5Hz/52.5Hz dual frequency
External HV: UST: 5A max, GST: 12kV/5A max, 38-72Hz
Test Time: 30s typical (may vary in different test mode)
Power Supply: 95V~130V,180V~260V,50Hz/60Hz
( Single phase power supply or generator )
Display: 128×64 dot matrix
Printer: Thermal printer
Communication Port: RS-232
Operating Temperature: -10℃~50℃
storage Temperature: -20℃~60℃
Humidity: <90% non-condensing
Dimensions: 460mm(L)×350mm(W)×340mm(H)
Weight: Main unit: 23kg , cable: 3.5kg
Quality Assured In Factory
Well designed
Each part or component is checked carefully
-20℃ low temperature test ,
60℃ high temperature test
Shock & Vibration test
Aging test
72 hours energized
21 days in natural state
Order Information
Item Art. No.
DF902A
DF902A,main unit, test cables, Additional paper roll and fuse
Lead time: 6 weeks
Warranty: 36 months